No rule says a school must have security shutters. The Department for Education's guidance asks each school to assess its own risks and choose proportionate measures, and its list of examples names access control, perimeter fencing, security lighting, security glazing and alarms, not shutters. When a school does fit them, the useful benchmarks come from elsewhere: Secured by Design asks for a shutter certified to at least LPS 1175 Issue 7 Security Rating 1 (or Issue 8 rating A1 under its 2025 guide), and higher for delivery doors. A shutter must never stop a fire exit being opened easily and immediately while people are inside, powered shutters need anti-trap safety features and, where needed, manual operation, and Building Bulletin 100 says shutters across an escape route should close on heat, not on the fire alarm.

Key points

  • The DfE guidance is risk based. A shutter is a choice the school justifies in its own security risk assessment, not a requirement.
  • Secured by Design's minimum for shutters on doors and windows is LPS 1175 Issue 7 SR1, or LPS 1175 Issue 8 A1 in its 2025 Commercial guide. Delivery doors with no other door start at Issue 7 SR2 in the schools guide and Issue 8 B3 in the 2025 guide.
  • Emergency exits must open easily and immediately for anyone who needs them. A shutter that is down and locked over an exit while the school is occupied fails that test.
  • Powered shutters fall under the workplace rules on powered doors: anti-trap features, and manual operation where safety needs it if the shutter does not open on power failure.
  • The governing body, academy trust or local authority, as the employer and responsible person, owns the decision. The installer does not.

Start with the risk assessment, not the shutter

The DfE's school and college security guidance, last updated in July 2026, puts the decision on the school: name a competent person to lead on security, assess the risks, and pick measures that are proportionate to the threat, its likelihood and its impact on school life. Its companion list of preventative measures gives CCTV, access control, perimeter fencing, security lighting, security glazing and intruder alarms as examples. Shutters are not on it.

That matters for a premises manager being sold shutters on a new block. If the risk assessment shows repeated glass damage, break-ins to an IT suite or arson attempts on one elevation, a certified shutter on those openings is easy to justify. If the problem is daytime access through the front gate, a shutter over a classroom window does nothing for it.

Building Bulletin 100, the DfE's fire design guide for schools, adds the arson angle. Using fire statistics for 2000 to 2005, it reports just over 1,300 school fires a year on average, with 56 percent classed as non-accidental and most of those likely to be arson. It also notes that the larger fires tend to happen out of hours, when someone can work undisturbed. Keeping intruders out of the building is one of its arson strategies, and it lists LPS 1175 as the standard for doors, windows and shutters.

What rating to ask for

Secured by Design publishes the ratings police designing out crime officers expect on new and refurbished buildings. Its New Schools guide from 2014 is still the school-specific one; its Commercial Design Guide 2025 is newer and lists the current issues of each standard. The two agree on the starting point and on when to go higher.

Minimum shutter ratings in Secured by Design guidance
OpeningNew Schools 2014Commercial Design Guide 2025 (current issues)
Roller shutter or grille over a door or windowLPS 1175 Issue 7 SR1 or STS 202 BR1LPS 1175 Issue 8 A1, LPS 2081 Issue 1 A, STS 202 Issue 12 BR1, STS 222 Issue 4 BR1(S) or LPS 1673 AR.A60, or above. Issue 7 SR1 stays acceptable until a date still to be set
Roller shutter door for deliveries where no other door is presentLPS 1175 Issue 7 SR2 or STS 202 BR2LPS 1175 Issue 8 B3, LPS 2081 Issue 1 B, STS 202 Issue 12 BR2, STS 222 Issue 4 BR2(S) or LPS 1673 AR.A180, or above
Windows on a vulnerable elevationEither certified windows, or minimum windows plus a certified shutter or grilleNot school specific
  • Both guides say the minimum is generally enough where the shutter stops minor damage and glass breakage, is alarmed on a site with access control and patrols, closes off a recess, or protects a door or window that is already high security.
  • Both say a higher rating may be needed depending on the type and level of crime risk, the location and the security of the opening behind it, and that the police officer will justify that in writing.
  • The 2014 schools guide notes that shutters may only be needed on particularly vulnerable elevations, not the whole building.
  • Check any certificate yourself on RedBook Live for the exact product, size and issue. Our guide to LPS 1175 ratings explains how the test works.

Fire exits: where school shutters go wrong

This is the clash Building Bulletin 100 itself flags: easy evacuation in a fire can conflict with controlling entry and exit for security, and measures against intruders can also slow the fire and rescue service. It says to resolve these conflicts at design stage, not with fixes after handover, and points to police architectural liaison officers for advice.

The rules a school shutter has to meet on escape routes
RuleWhere it comes fromWhat it means for a shutter
Emergency doors must not be locked or fastened so they cannot be easily and immediately opened by anyone who needs themFire Safety Order 2005, article 14(2)(f)A shutter over an exit door must be up whenever people are inside, or the exit is not an exit
Routes to emergency exits and the exits themselves are kept clear at all timesFire Safety Order 2005, article 14(1)No shutter box, guide or bottom rail that narrows an exit route
Shutters across a means of escape should be released only by a heat sensor near the door, not by smoke detectors or the fire alarm (unless part of a smoke reservoir)Building Bulletin 100, Appendix CA fire alarm test must not drop a shutter across a corridor full of pupils
Rolling shutters in compartment walls should be openable and closable by hand by the fire service without a ladderBuilding Bulletin 100, section 8.4.5Plan the manual override position before fitting

The motor: safeguarding means anti-trap and a manual route

A school is a workplace, so a powered shutter is a powered door under regulation 18 of the Workplace (Health, Safety and Welfare) Regulations 1992. Any powered door or gate must have suitable and effective features to stop it trapping anyone, an upward opening door must have a device to stop it falling back, and where health or safety needs it, a powered door must be openable by hand unless it opens automatically when the power fails.

Secured by Design's 2025 guide adds the security side: in an emergency it must be possible to close electrically operated shutters quickly from a safe place inside the building. For a school that points to a fixed key switch or control in a staff area, not a handset that can go missing, and to obstruction detection on any shutter children walk under. A battery or manual backup matters for the same reason; our guide to shutters in a power cut covers the options.

Who signs it off

Under the Fire Safety Order the responsible person for a workplace is the employer. In a school that is usually the local authority, the governing body or the academy trust, depending on the type of school, and the DfE guidance expects a competent person to lead on security alongside the designated safeguarding lead. The installer's job is to supply a shutter that meets the specification; deciding where shutters go, and checking that the fire risk assessment still holds, stays with the school.

Martyn's Law will add to this. Under the Terrorism (Protection of Premises) Act 2025, a primary or secondary school where 200 or more people may be present at once is treated as standard duty premises, with the governing body (or the proprietor where there is none, or the local authority for a pupil referral unit) as the responsible person. The standard duty is about procedures, including evacuation, moving people to a safer place and preventing people entering or leaving. The Home Office and DfE say the duty comes into force in 2027. A shutter that can be closed quickly from inside may form part of a lockdown plan, but the Act asks for procedures, not shutters.

Planning and the building itself

Works that affect only the interior of a building, or that do not materially affect its external appearance, are not development under section 55 of the Town and Country Planning Act 1990. An internal grille behind a window is usually in that first group. A box and guides on the outside of a school usually change its appearance, and schools have no householder permitted development rights, so ask the local planning authority before ordering. Listed school buildings need listed building consent for changes that affect their character; see our planning guide for external shutters for how the rules work.

Both Secured by Design guides say shutters on new buildings should be built into the fabric rather than bolted on afterwards, and the schools guide asks for reinforced fixing points for shutters and roller boxes where needed, so they cannot be removed to get in.

A checklist for the premises manager

  1. Write down which risk the shutter answers, from your security risk assessment: glass damage, burglary, arson on one elevation, or out of hours access to a specific room.
  2. Mark every shutter position on the fire plan and remove any that sit over an exit door or across an escape route unless the fire risk assessor has agreed the arrangement.
  3. Ask for the certificate number and issue (LPS 1175 Issue 7 or 8, or the other standards above) and check it on RedBook Live for that size of shutter.
  4. Ask how the motor stops trapping a child, how it opens in a power cut, and where the inside control for quick closing will be.
  5. Agree who keeps the keys or switch, who opens the shutters each morning before the building is occupied, and what happens if that person is off.
  6. Send the plan to the local planning authority if the shutter goes on the outside, and to your insurer, which may specify a rating. Our guide to insurance and shutters explains why the wording matters.
  7. Book servicing in the contract. A shutter that jams half open is neither secure nor safe.

How this differs from a shop

A shopfront shutter protects one frontage and is closed by the person locking up. A school has many openings, many staff, children under the shutters at the start and end of the day, and a duty to keep exits usable. That is why the fire and powered door rules carry more weight here than the slat profile. For shopfronts see our shop security shutters guide, and for prices on certified shutters see security shutters.

Frequently asked questions

Do schools have to have security shutters?

No. The DfE guidance asks schools to assess their own security risks and choose proportionate measures. Its examples are access control, fencing, lighting, security glazing and alarms. Shutters are an option where the risk assessment supports them.

What security rating should a school shutter have?

Secured by Design's New Schools guide asks for at least LPS 1175 Issue 7 Security Rating 1 or STS 202 BR1 on shutters over doors and windows, and SR2 or BR2 for delivery shutter doors with no other door. Its 2025 Commercial guide lists LPS 1175 Issue 8 A1 and B3 as the current equivalents.

Can a roller shutter be fitted over a fire exit in a school?

Only if the exit can still be opened easily and immediately whenever people are inside. Article 14 of the Fire Safety Order 2005 says emergency doors must not be locked or fastened so they cannot be. In practice the shutter must be fully open during the school day, and the fire risk assessor should agree the arrangement.

Should a school shutter close when the fire alarm goes off?

Not across an escape route. Building Bulletin 100 says shutters across a means of escape should be released only by a heat sensor near the door, not by smoke detectors or the fire alarm, unless the shutter is designed to form part of a smoke reservoir.

Who is responsible for school shutters?

The employer, which is the responsible person under the Fire Safety Order: the local authority, governing body or academy trust depending on the school. The DfE expects a competent person to lead on security.

Does Martyn's Law require schools to fit shutters?

No. Schools with 200 or more people present are standard duty premises under the Terrorism (Protection of Premises) Act 2025, which asks for procedures such as evacuation, invacuation and lockdown. The government says it comes into force in 2027.

Sources and further reading